Table 3 Results of power flow calculations for the transformer in D, yn1 connection

From: Three-phase distribution transformer connections modeling based on matrix operation method by phase-coordinates

No Results
Bus 2 (Voltage/V & angle/°) Bus 3 (Voltage/V & angle/°)
1 A 12,364/29.8 A 13,792/27.7
B 12,391/ − 90.5 B 13,733/ − 93.5
C 12,333/149.6 C 13,641/145.4
2 A 12,363/29.78 A 13,792/27.71
B 12,391/ − 90.5 B 13,732/ − 93.50
C 12,332/149.56 C 13,640/145.43
3 A 12,289/30.52 A 13,164/27.7
B 12,284/ − 89.56 B 13,208/ − 94.21
C 12,220/150.30 C 12,939/145.04
4 A 12,287/30.52 A 13,162/27.49
B 12,282/ − 89.56 B 13,206/ − 94.21
C 12,218/150.31 C 12,937/145.04
5 A 12,343/29.8 A 13,782/27.7
B 12,376/ − 90.5 B 13,723/ − 93.5
C 12,314/149.6 C 13,631/145.4
6 A 12,296/30.02 A 13,385/27.52
B 12,341/ − 90.23 B 13,498/ − 94.02
C 12,254/149.87 C 13,153/145.16