Table 5 Results for power flow calculations for the transformers (YN, yn 0 connection) in different loads

From: Three-phase distribution transformer connections modeling based on matrix operation method by phase-coordinates

No Load Bus2 (V./Angle) Bus3 (V./Angle.)
1 1.2S1 A 7153/ − 0.10 A 13,725/ − 2.59
B 7103/ − 120.3 B 13,504/ − 124.0
C 7110/119.1 C 13,484/114.1
1.4S1 A 7145/ − 0.12 A 13,607/ − 2.59
B 7086/ − 120.3 B 13,338/ − 124.7
C 7090/119.0 C 13,301/113.0
1.6 S1 A 7137/ − 0.12 A 13,486/ − 3.54
B 7067/ − 120.4 B 13,164/ − 125.5
C 7069/118.8 C 13,104/111.9
6 1.2S1 A 7152/ − 0.11 A 13,814/ − 1.98
B 7104/ − 120.3 B 13,520/ − 123.4
C 7111/119.1 C 13,641/115.2
1.4S1 A 7144/ − 0.12 A 13,715/ − 2.33
B 7086/ − 120.4 B 13,363/ − 124.0
C 7091/119.0 C 13,489/113.1
1.6S1 A 7136/ − 0.15 A 13,615/ − 3.54
B 7069/ − 120.4 B 13,199/ − 125.5
C 7072/118.8 C 13,328/112.1