Skip to main content

Table 1 Primary communication parameters of dual-mode communication module

From: Heterogeneous field network for power distribution grid based on HPLC and RF adaptive communications technology

Mode

Project

Technical indicators

HPLC communication

Operating frequency band

2–12 MHz, support segmentation

Power spectrum density

In-band < −45 dBm/Hz; Out-band < −75 dBm/Hz

Modulation mode

Multicarrier OFDM modulation

Transmission rate

Adaptive rate

Anti-attenuation performance

 > 85 dB

RF communication

Operating frequency band

470–510 MHz

Modulation mode

FSK, baseband signal is filtered by GFSK

Modulation frequency deviation

10 kHz (@ 20kbps); 40 kHz (@ 100kps)

Transmission Rate

Support 20kbps and 100kbps