Skip to main content

Table 4 Test data of three kinds of field network in jobsite

From: Heterogeneous field network for power distribution grid based on HPLC and RF adaptive communications technology

Station

Network type

NSR (%)

RAT

RSR (%)

CDC (%)

NO.3

Dual-mode

99.65

0.27

99.12

4.66

HPLC

98.12

0.45

97.34

7.88

RF

95.21

0.76

95.34

8.35

NO.4

Dual-mode

99.78

0.24

99.31

4.79

HPLC

98.64

0.59

96.23

11.59

RF

96.38

0.84

94.39

12.86

NO.6

Dual-mode

99.56

0.20

99.41

7.16

HPLC

99.23

0.53

97.63

19.05

RF

97.62

0.82

93.12

23.43